| Abstract:This study conducted an in-depth analysis of the distribution network system upgrade at a paper mill. The main distribution networks in the northern and southern plant zones exhibited a fixed 30° phase difference. By analyzing the causes of the phase difference and its potential effects and risks on distribution networks, and after comprehensive evaluation of field operating conditions and safety reliability, a transformer connection group adjustment approach was proposed through multi-scenario comparisons to eliminate phase differences in distribution network loop closure retrofitting schemes. |