本文二维码信息
二维码(扫一下试试看!)
Analysis of the Causes of Phase Angle Difference in the Distribution Networks of a Paper Mill and Design of the Loop Closure Retrofitting Scheme
Received:October 20, 2025  Revised:November 11, 2025
DOI:10.11980/j.issn.0254-508X.2026.04.028
Key Words:paper mill  distribution network  phase angle difference  loop closure
Author NameAffiliationPostcode
GAN Jingchun* China CEC Engineering Corporation, Changsha, Hu’nan Province, 410114)
(corresponding author:E-mail:278520081@qq.com 
410114
Hits: 1006
Download times: 154
Abstract:This study conducted an in-depth analysis of the distribution network system upgrade at a paper mill. The main distribution networks in the northern and southern plant zones exhibited a fixed 30° phase difference. By analyzing the causes of the phase difference and its potential effects and risks on distribution networks, and after comprehensive evaluation of field operating conditions and safety reliability, a transformer connection group adjustment approach was proposed through multi-scenario comparisons to eliminate phase differences in distribution network loop closure retrofitting schemes.
View Full Text  HTML  View/Add Comment  Download reader