本文二维码信息
二维码(扫一下试试看!)
Short Circuit Current Suppression Measures for Owned Power Plant in Paper Mill
Received:November 22, 2024  
DOI:10.11980/j.issn.0254-508X.2025.04.019
Key Words:paper mill  short circuit current  current limiting reactor  fast current limiting device
Author NameAffiliationPostcode
QIU Jie* China CEC Engineering Corporation, Changsha, Hu’nan Province, 410114 410114
ZUO Dongyang Jiangsu New Power (Shuyang) Thermal Power Co., Ltd., Shuyang, Jiangsu Province, 223600 223600
Hits: 2642
Download times: 962
Abstract:This research focused on investigating the issue of excessive short circuit current levels (up to 10 kV busbars) for owned power plant in paper mill, which exceeded the conventional circuit-breaker interrupting capacity. A comparative analysis was conducted on the operational principles of various short circuit current limiting schemes, with particular emphasis on evaluating their technical merits and practical limitations. Through systematic evaluation, the study proposed implementing a hybrid solution at the generator terminals consisting of a series-connected current limiting reactor combined with a parallel fast current limiting device. This integrated approach was demonstrated to enhance system stability and achieve reliable fault protection under extreme fault conditions while adhering to standard equipment withstand requirements.
View Full Text  HTML  View/Add Comment  Download reader