本文二维码信息
二维码(扫一下试试看!)
Discussion on Anti Surge Control Mode of Steam Compressor
Received:November 22, 2019  
DOI:10.11980/j.issn.0254-508X.2020.04.009
Key Words:compressor  surge  performance curve  warning  vibration
Fund Project:(2)本项目蒸汽压缩机的性能曲线见图4。
Author NameAffiliationPostcode
HUANG Guangming China CEC Engineering Corporation, Changsha, Hu’nan Province, 410004 410004
RAO Jia China CEC Engineering Corporation, Changsha, Hu’nan Province, 410004 410004
ZHONG Zhihui China CEC Engineering Corporation, Changsha, Hu’nan Province, 410004 410004
Hits: 20413
Download times: 4397
Abstract:In the evaporation crystallization process system(MVR)of salt production and wastewater treatment, due to the narrow working area of the steam compressor, it was easy to have problems of interlock protection and automatic control, such as liquid hammer, frequent surge, over large vibration value, etc. measures such as controlling the pressure and temperature at the outlet of the compressor, setting the anti surge early warning control program, surge screen alarm, and increasing the return pipeline were adopted on DCS. When compressor surge occured, DCS could automatically open surge valve by means of surge warning program or manually open surge valve by means of surge alarm screen, so as to avoid compressor surge and liquid hammer.
View Full Text  HTML  View/Add Comment  Download reader